Turner Strategic Technologies
Joint Base Lewis-McChord’s distribution system is a single-point-grounded system operating at 13,800 volts. Joint Base Lewis-McChord has adopted Tacoma Public Utilities (TPU) design criteria as “industry standards” for utility construction.
Services Employed:
- $1.2MM contract
- Hundreds of Housing Units Serviced
- 165- New Guy Poles
- 244-Cross Arms
- 65- Pole Mount Trans
- 608- Insulators
- 66,396' FT- ACSR Bare Wire Primary
- 37, 742' FT- TRIPLEX Secondary w/full size ACSR messenger
- 13, 100' FT- Solid Wire
General Overhead construction requirements:
- All new construction shall be underground unless dictated otherwise by special circumstance.
- Pole-mounted three-phase transformer banks shall be no larger than 3-75KVA. Pole- mounted single-phase transformers shall be no larger than 100KVA.
- Pole-mounted transformers shall have separate ground for lightning arrestors, case grounds, and neutral conductor. (Neutral ground is isolated per NESC.)
- Construction shall be Grade B per the National Electrical Safety Code (NESC), ANSI C2.
- Size, sag, and support overhead conductors per NESC and TPU standards.
- Lightning arresters, appropriately sized, shall be provided at all risers, dead-end poles, and at each overhead and pad-mounted transformer. All cross-arms shall be 9 foot in
- length unless application requires longer/larger arms.
- Primary risers shall be constructed using alley-arm construction with arms parallel to main line
- Splices and dead-ends shall be of the automatic type. Deadends shall be polymer-type.
- Stirrups and other connections shall be made using compression type connectors listed for the application.
- Fused disconnects shall be of the loadbreak type.
- Power poles shall be rated Class 2.
- Secondary conductor connections shall be made using compression-type connectors.
More Power work
Related projects
Power
JBLM Grounding and Lightning Protection, 10 Facilities
JBLM, WA
Grounding and lightning protection system upgrade across ten facilities at Joint Base Lewis-McChord, enhancing the safety and compliance of critical military buildings against lightning...
View projectPower
Iron Mountain Quarry Line Extension
Granite Falls, WA
Half mile electrical line extension at an operating rock quarry in Granite Falls, built overhead and underground up a rock face to a new...
View projectPower
JBLM Overhead Neutral Replacement, McChord Field
JBLM, WA
Replacement of primary neutral conductor across the McChord Field distribution system at Joint Base Lewis-McChord, performed for City Light & Power JBLM under its...
View project
Planning something similar?
Our estimators and project managers can walk you through approach, schedule and scope.